Wisdom Achieves Dreams, Reliability Determines the Future
Signal Isolators
REB1IS-110
763032
1
Input | Output | |||||
Nominal value(voltage) | 0~75mV, 0~5V, 0~10V, 0~300V | Analog input voltage | 0~5V、0~10V | |||
Nominal value(current) | 0~20mA, 4~20mA | Analog input current | 0~20mA、4~20mA | |||
Continuous power input | 120% Nominal value | Load | Current output:≤750Ω, voltage output≥2kΩ | |||
Impedance | Current input terminal ≤100Ω, Voltageinput terminal ≥100kΩ | Output protection | Short circuit protection | |||
Rated data | Max. output current | 25mA | ||||
Feature | ||||||
Accuracy grade | ±0.2% | |||||
Temp drift | ≤250ppm/°CF.S | |||||
Insulation resistance | ≥100MΩ(500VDC·1min) | |||||
Power frequency withstanding voltage | 2kV/50Hz·1min(input-output) 2kV/50Hz·1min(output-power supplies) 2kV/50Hz·1min(input-power supplies) 2kV/50Hz·1min(input-ground) | |||||
EMC standards | GB/t 17626 IEC61326 | |||||
Power supplies | ||||||
Rated voltage | 24VDC 16~60VAC/DC 100~240VAC/DC | |||||
voltage range | 24VDC±20% 16~60VAC/DC 85~265VAC/DC | |||||
Power consumption | ≤3W ≤3VA/3W ≤5VA/5W | |||||
Environment | ||||||
Operating ambient temp | -25℃~+55℃ | |||||
Storage and transport temp | -40℃~+85℃ | |||||
Relative humidity | 5%~90%(no condensation and ice inside shell), when temp reaches +40℃~+55℃,relative air humidity is no more than 50% | |||||
Atmospheric pressure | 80kPa~110kPa(altitude is less than 2000m) | |||||
Overall dimension | ||||||
Installation mode | Din rail RTR35/RTR32 | |||||
Size | 94/24/119mm(1 pole output);94/34/119(2 pole output) | |||||
Weight | 150g | |||||
Tightening torque | 0.8Nm | |||||
Ordering data | ||||||
Input signal | 0~20mADC | |||||
Output | 0~20mADC | |||||
Auxiliary power supplies | No |